FY 2017 Reliability Summary |
|
|
|
|
|
|
|
|
|
|
|
Reliability
Budget |
|
|
|
|
|
|
System |
Unavailability
Allotment |
|
Number of Faults |
Mean Time to Beam
Loss |
Faults Per |
|
|
Day |
RF |
0.5% |
|
|
200 |
0.12 |
|
|
Diagnostics |
0.1% |
|
|
800 |
0.03 |
|
|
PS |
0.5% |
|
|
200 |
0.12 |
|
|
Controls |
0.3% |
|
|
500 |
0.05 |
|
|
Network |
0.1% |
|
|
4800 |
0.01 |
|
|
Interlocks |
0.2% |
|
|
800 |
0.03 |
|
|
Accelerator |
0.1% |
|
|
2400 |
0.01 |
|
|
Beamline |
0.1% |
|
|
2400 |
0.01 |
|
|
Radiation |
0.1% |
|
|
1600 |
0.02 |
|
|
MOM |
0.4% |
|
|
480 |
0.05 |
|
|
S&A |
0.0% |
|
|
48000 |
0.00 |
|
|
Operations & Analysis |
0.1% |
|
|
4800 |
0.01 |
|
|
Physics |
0.0% |
|
|
48000 |
0.00 |
|
|
ID-FE |
0.1% |
|
|
4800 |
0.01 |
|
|
ID-FE/MD |
not specified |
|
|
|
|
|
|
ID-FE/XFE |
not specified |
|
|
|
|
|
|
Utilities |
0.3% |
|
|
800 |
0.03 |
|
|
Electrical - APS |
0.1% |
|
|
2400 |
0.01 |
|
|
Electrical - ANL |
0.2% |
|
|
2400 |
0.01 |
|
|
Cooling - ANL |
0.1% |
|
|
2400 |
0.01 |
|
|
Other |
0.2% |
|
|
1200 |
0.02 |
|
|
Unidentified |
0.1% |
|
|
1200 |
0.02 |
|
|
Total |
2.9% |
|
|
49.6 |
0.48 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Data through Run 2017-2 |
|
|
|
|
|
|
|
|
|
|
|
|
FY 2017 Actual |
Unavailability |
Unavailability |
Number |
Mean Time |
Faults Per |
|
|
Percent |
Hours |
of Faults |
to Beam Loss |
Day |
RF |
0.35% |
17.50 |
7 |
692.6 |
0.03 |
User Downtime Hours |
151.70 |
Diagnostics |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
PS |
0.39% |
19.28 |
13 |
372.9 |
0.06 |
Scheduled Hours |
5000 |
Controls |
0.03% |
1.47 |
1 |
4848.3 |
0.00 |
|
|
Network |
0.00% |
0.00 |
0 |
|
0.00 |
Delivered Hours |
4848.3 |
Safety Interlocks |
0.04% |
1.95 |
2 |
2424.1 |
0.01 |
|
|
Radiation Monitors |
0.00% |
0.00 |
0 |
|
0.00 |
User Availability |
96.97% |
MOM |
0.17% |
8.70 |
9 |
538.7 |
0.04 |
|
|
Vacuum |
0.37% |
18.60 |
0 |
|
0.00 |
Longest period w/out a fault |
527.72 |
Operations |
0.05% |
2.27 |
0 |
|
0.00 |
|
|
ID-FE |
0.01% |
0.52 |
0 |
|
0.00 |
|
|
ID-FE/MD |
0.00% |
|
|
|
0.00 |
|
|
ID-FE/XFE |
0.00% |
|
|
|
0.00 |
|
|
Utilities |
0.02% |
1.07 |
2 |
2424.1 |
0.01 |
|
|
Electrical - APS |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
Electrical - ANL |
0.02% |
1.07 |
2 |
2424.1 |
0.01 |
|
|
Cooling - ANL |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
Other |
1.59% |
79.67 |
1 |
4848.3 |
0.00 |
|
|
Unidentified |
0.01% |
0.67 |
1 |
4848.3 |
0.00 |
|
|
APS-U |
|
0.67 |
1 |
4848.3 |
0.00 |
|
|
Total |
3.05% |
152.35 |
36 |
134.7 |
0.18 |
|
|
|
|
|
|
|
|
|
|
Run 2016-3 |
Unavailability |
Unavailability |
Number |
Mean Time |
Faults Per |
|
|
Percent |
Hours |
of Faults |
to Beam Loss |
Day |
|
|
|
|
|
|
|
|
RF |
0.77% |
12.02 |
4 |
384.8 |
0.06 |
User Downtime Hours |
21.67 |
Diagnostics |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
PS |
0.26% |
4.10 |
6 |
256.6 |
0.09 |
Scheduled Hours |
1561.0 |
Controls |
0.09% |
1.47 |
1 |
1539.3 |
0.02 |
Delivered Hours |
1539.3 |
Network |
|
0.00 |
0 |
|
|
|
|
Safety Interlocks |
0.12% |
1.95 |
2 |
769.7 |
0.03 |
User Availability |
98.61% |
Radiation Monitors |
0.00% |
|
|
|
0.00 |
|
|
MOM |
0.03% |
0.50 |
1 |
1539.3 |
0.02 |
|
|
Vacuum |
0.00% |
|
|
|
0.00 |
Longest period w/out a fault |
351.94 |
Operations |
0.07% |
1.10 |
0 |
|
0.00 |
|
|
ID-FE |
0.03% |
0.52 |
0 |
|
0.00 |
|
|
ID-FE/MD |
0.07% |
1.10 |
|
|
0.00 |
|
|
ID-FE/XFE |
0.07% |
1.10 |
|
|
0.00 |
|
|
Utilities |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
Electrical - APS |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
Electrical - ANL |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
Cooling - ANL |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
Other |
0.00% |
|
|
|
0.00 |
|
|
Unidentified |
0.00% |
0.00 |
0 |
|
|
|
|
Total |
1.41% |
21.65 |
14 |
110.0 |
0.22 |
|
|
|
|
|
|
|
|
|
|
Run 2017-1 |
Unavailability |
Unavailability |
Number |
Mean Time |
Faults Per |
|
|
Percent |
Hours |
of Faults |
to Beam Loss |
Day |
|
|
|
|
|
|
|
|
RF |
0.00% |
0.00 |
0 |
|
0.00 |
User Downtime Hours |
20.95 |
Diagnostics |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
PS |
0.73% |
12.57 |
5 |
339.6 |
0.07 |
Scheduled Hours |
1719 |
Controls |
0.00% |
|
|
|
0.00 |
Delivered Hours |
1698.0 |
Network |
0.00% |
|
|
|
|
|
|
Safety Interlocks |
0.00% |
|
|
|
0.00 |
User Availability |
98.8% |
Radiation Monitors |
0.00% |
|
|
|
0.00 |
|
|
MOM |
0.40% |
6.95 |
6 |
283.0 |
0.08 |
|
|
Vacuum |
0.00% |
|
|
|
0.00 |
Longest period w/out a fault |
361.28 |
Operations |
0.05% |
0.88 |
0 |
|
0.00 |
|
|
ID-FE |
0.00% |
|
|
|
0.00 |
|
|
Utilities |
0.03% |
0.55 |
1 |
1698.0 |
0.01 |
|
|
Electrical - APS |
0.00% |
|
|
|
0.00 |
|
|
Electrical - ANL |
0.03% |
0.55 |
1 |
1698.0 |
0.01 |
|
|
Cooling - ANL |
0.00% |
|
|
|
0.00 |
|
|
Other |
0.00% |
|
|
|
0.00 |
|
|
Unidentified |
0.00% |
|
|
|
0.00 |
|
|
Total |
1.23% |
20.95 |
12 |
141.5 |
0.17 |
|
|
|
|
|
|
|
|
|
|
Run 2017-2 |
Unavailability |
Unavailability |
Number |
Mean Time |
Faults Per |
|
|
Percent |
Hours |
of Faults |
to Beam Loss |
Day |
|
|
|
|
|
|
|
|
RF |
0.32% |
5.48 |
3 |
513.1 |
0.05 |
User Downtime Hours |
109.08 |
Diagnostics |
0.00% |
0.00 |
0 |
|
0.00 |
|
|
PS |
0.15% |
2.62 |
2 |
769.7 |
0.03 |
Scheduled Hours |
1720.0 |
Controls |
0.00% |
0.00 |
0 |
|
0.00 |
Delivered Hours |
1610.9 |
Network |
0.00% |
0.00 |
0 |
|
|
|
|
Safety Interlocks |
0.00% |
0.00 |
0 |
|
0.00 |
User Availability |
93.7% |
Radiation Monitors |
0.00% |
|
0 |
|
0.00 |
|
|
MOM |
0.07% |
1.25 |
2 |
769.7 |
0.03 |
|
|
Vacuum |
1.08% |
18.60 |
0 |
|
0.00 |
Longest period w/out a fault |
527.72 |
Operations & Analysis |
0.02% |
0.28 |
0 |
|
0.00 |
|
|
Physics |
0.00% |
|
|
|
0.00 |
|
|
ID-FE |
0.00% |
|
|
|
0.00 |
|
|
ID-FE/MD |
0.00% |
|
|
|
0.00 |
|
|
UES |
0.00% |
|
|
|
0.00 |
|
|
Utilities |
0.03% |
0.52 |
1 |
1539.3 |
0.02 |
|
|
Electrical - APS |
0.00% |
|
|
|
0.00 |
|
|
Electrical - ANL |
0.03% |
0.52 |
1 |
1539.3 |
0.02 |
|
|
Cooling - ANL |
0.00% |
|
|
|
0.00 |
|
|
Other |
4.63% |
79.67 |
1 |
1539.3 |
0.02 |
|
|
Unidentified |
0.04% |
0.67 |
1 |
1539.3 |
0.02 |
|
|
APS-U |
0.00% |
|
|
|
0.00 |
|
|
Total |
6.34% |
109.08 |
10 |
161.1 |
0.15 |
|
|
|
|
|
|
|
|
Updated |